Keadby
Grid supply point in Yorkshire (Northern Powergrid)
Northern Powergrid Embedded Capacity Register 1MW and Over, September 2026 edition
Capacity by technology
| Technology | Sites | Capacity | Connected | Accepted to connect |
|---|---|---|---|---|
| Storage | 10 | 867 MW | 52 MW | 815 MW |
| Solar | 30 | 858 MW | 105 MW | 753 MW |
| Wind | 8 | 323 MW | 133 MW | 190 MW |
| Gas and other fossil | 9 | 205 MW | 201 MW | 4 MW |
| Bioenergy and waste | 8 | 138 MW | 75 MW | 63 MW |
| Other or not stated | 1 | 1.1 MW | 1.1 MW | – |
Storage capacity: 4 sites here state 627 MWh, 627 MWh accepted to connect.
Each site is grouped by its first energy source, as the register names it.
How busy is each primary substation?
Each primary substation at this grid supply point in the September 2026 edition, under the bulk supply point its register gives. Select a row to see its sites.
Site, company and substation names are shown as they appear in the registers, including capitalisation.
| Primary substation | Bulk supply point | Sites | Connected | Accepted to connect | |||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Elm Tree Hybrid | 1 | – | 395 MW | ||||||||||||||||||||||||||
1 site, 395 MW: 395 MW accepted to connect
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | – | 80 MW | ||||||||||||||||||||||||||
1 site, 80 MW: 80 MW accepted to connect
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | – | 36 MW | ||||||||||||||||||||||||||
1 site, 36 MW: 36 MW accepted to connect
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | – | 32 MW | ||||||||||||||||||||||||||
1 site, 32 MW: 32 MW accepted to connect
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | – | 30 MW | ||||||||||||||||||||||||||
1 site, 30 MW: 30 MW accepted to connect
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | 20 MW | – | ||||||||||||||||||||||||||
1 site, 20 MW: 20 MW connected
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | 16.2 MW | – | ||||||||||||||||||||||||||
1 site, 16.2 MW: 16.2 MW connected
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | 16 MW | – | ||||||||||||||||||||||||||
1 site, 16 MW: 16 MW connected
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | 12.2 MW | – | ||||||||||||||||||||||||||
1 site, 12.2 MW: 12.2 MW connected
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | 4.6 MW | – | ||||||||||||||||||||||||||
1 site, 4.6 MW: 4.6 MW connected
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | – | 1.7 MW | ||||||||||||||||||||||||||
1 site, 1.7 MW: 1.7 MW accepted to connect
| |||||||||||||||||||||||||||||
| Scunthorpe North | 1 | 1 MW | – | ||||||||||||||||||||||||||
1 site, 1 MW: 1 MW connected
| |||||||||||||||||||||||||||||
| Santon Solar Farm | 1 | – | 200 MW | ||||||||||||||||||||||||||
1 site, 200 MW: 200 MW accepted to connect
| |||||||||||||||||||||||||||||
| Scawby Brook | 2 | 97.9 MW | – | ||||||||||||||||||||||||||
2 sites, 97.9 MW: 97.9 MW connected
| |||||||||||||||||||||||||||||
| Scawby Brook | 1 | – | 79.9 MW | ||||||||||||||||||||||||||
1 site, 79.9 MW: 79.9 MW accepted to connect
| |||||||||||||||||||||||||||||
| Santon | 1 | 40 MW | – | ||||||||||||||||||||||||||
1 site, 40 MW: 40 MW connected
| |||||||||||||||||||||||||||||
| Santon | 1 | – | 20 MW | ||||||||||||||||||||||||||
1 site, 20 MW: 20 MW accepted to connect
| |||||||||||||||||||||||||||||
| Santon | 1 | – | 20 MW | ||||||||||||||||||||||||||
1 site, 20 MW: 20 MW accepted to connect
| |||||||||||||||||||||||||||||
| Santon | 3 | 2.4 MW | 11.4 MW | ||||||||||||||||||||||||||
3 sites, 13.8 MW: 2.4 MW connected, 11.4 MW accepted to connect
| |||||||||||||||||||||||||||||
| Santon | 1 | – | 13 MW | ||||||||||||||||||||||||||
1 site, 13 MW: 13 MW accepted to connect
| |||||||||||||||||||||||||||||
| Santon | 3 | 5.5 MW | 3.5 MW | ||||||||||||||||||||||||||
3 sites, 9 MW: 5.5 MW connected, 3.5 MW accepted to connect
| |||||||||||||||||||||||||||||
| Santon | 1 | 8 MW | – | ||||||||||||||||||||||||||
1 site, 8 MW: 8 MW connected
| |||||||||||||||||||||||||||||
| Santon | 1 | – | 5 MW | ||||||||||||||||||||||||||
1 site, 5 MW: 5 MW accepted to connect
| |||||||||||||||||||||||||||||
| Broughton | 1 | 123 MW | – | ||||||||||||||||||||||||||
1 site, 123 MW: 123 MW connected
| |||||||||||||||||||||||||||||
| Wold Newton | 3 | 17 MW | 15 MW | ||||||||||||||||||||||||||
3 sites, 32 MW: 17 MW connected, 15 MW accepted to connect
| |||||||||||||||||||||||||||||
| Wold Newton | 1 | – | 30 MW | ||||||||||||||||||||||||||
1 site, 30 MW: 30 MW accepted to connect
| |||||||||||||||||||||||||||||
| Wold Newton | 1 | 20 MW | – | ||||||||||||||||||||||||||
1 site, 20 MW: 20 MW connected
| |||||||||||||||||||||||||||||
| Wold Newton | 1 | 8 MW | – | ||||||||||||||||||||||||||
1 site, 8 MW: 8 MW connected
| |||||||||||||||||||||||||||||
| Wold Newton | 1 | 7.5 MW | – | ||||||||||||||||||||||||||
1 site, 7.5 MW: 7.5 MW connected
| |||||||||||||||||||||||||||||
| Wold Newton | 1 | 5 MW | – | ||||||||||||||||||||||||||
1 site, 5 MW: 5 MW connected
| |||||||||||||||||||||||||||||
| Keadby BESS | 1 | – | 99 MW | ||||||||||||||||||||||||||
1 site, 99 MW: 99 MW accepted to connect
| |||||||||||||||||||||||||||||
| Ludborough Solar Farm | 1 | – | 98 MW | ||||||||||||||||||||||||||
1 site, 98 MW: 98 MW accepted to connect
| |||||||||||||||||||||||||||||
| Haldenby Moor Wind Farm | 1 | – | 96 MW | ||||||||||||||||||||||||||
1 site, 96 MW: 96 MW accepted to connect
| |||||||||||||||||||||||||||||
| Scunthorpe South | 1 | 35 MW | – | ||||||||||||||||||||||||||
1 site, 35 MW: 35 MW connected
| |||||||||||||||||||||||||||||
| Scunthorpe South | 1 | 34.3 MW | – | ||||||||||||||||||||||||||
1 site, 34.3 MW: 34.3 MW connected
| |||||||||||||||||||||||||||||
| Scunthorpe South | 1 | – | 20 MW | ||||||||||||||||||||||||||
1 site, 20 MW: 20 MW accepted to connect
| |||||||||||||||||||||||||||||
| Scunthorpe South | 1 | – | 1.7 MW | ||||||||||||||||||||||||||
1 site, 1.7 MW: 1.7 MW accepted to connect
| |||||||||||||||||||||||||||||
| Vox Winterton BESS | 1 | – | 80 MW | ||||||||||||||||||||||||||
1 site, 80 MW: 80 MW accepted to connect
| |||||||||||||||||||||||||||||
| Keadby | 1 | – | 50 MW | ||||||||||||||||||||||||||
1 site, 50 MW: 50 MW accepted to connect
| |||||||||||||||||||||||||||||
| Keadby | 1 | – | 30 MW | ||||||||||||||||||||||||||
1 site, 30 MW: 30 MW accepted to connect
| |||||||||||||||||||||||||||||
| Keadby Windfarm | 1 | 68 MW | – | ||||||||||||||||||||||||||
1 site, 68 MW: 68 MW connected
| |||||||||||||||||||||||||||||
| HRS Biomass | 1 | – | 63 MW | ||||||||||||||||||||||||||
1 site, 63 MW: 63 MW accepted to connect
| |||||||||||||||||||||||||||||
| Lower Trent Wind Farm | 1 | – | 58.3 MW | ||||||||||||||||||||||||||
1 site, 58.3 MW: 58.3 MW accepted to connect
| |||||||||||||||||||||||||||||
| Caistor Solar | 1 | – | 49.9 MW | ||||||||||||||||||||||||||
1 site, 49.9 MW: 49.9 MW accepted to connect
| |||||||||||||||||||||||||||||
| Chapel Lane PV | 1 | – | 49.9 MW | ||||||||||||||||||||||||||
1 site, 49.9 MW: 49.9 MW accepted to connect
| |||||||||||||||||||||||||||||
| Grasby BESS | 1 | – | 49.9 MW | ||||||||||||||||||||||||||
1 site, 49.9 MW: 49.9 MW accepted to connect
| |||||||||||||||||||||||||||||
| Keadby Grid BESS | 1 | – | 49.9 MW | ||||||||||||||||||||||||||
1 site, 49.9 MW: 49.9 MW accepted to connect
| |||||||||||||||||||||||||||||
| Messingham Solar Park | 1 | – | 49.9 MW | ||||||||||||||||||||||||||
1 site, 49.9 MW: 49.9 MW accepted to connect
| |||||||||||||||||||||||||||||
| Blyton | 4 | 14.4 MW | – | ||||||||||||||||||||||||||
4 sites, 14.4 MW: 14.4 MW connected
| |||||||||||||||||||||||||||||
| Blyton | 1 | – | 8 MW | ||||||||||||||||||||||||||
1 site, 8 MW: 8 MW accepted to connect
| |||||||||||||||||||||||||||||
| Blyton | 4 | 7 MW | – | ||||||||||||||||||||||||||
4 sites, 7 MW: 7 MW connected
| |||||||||||||||||||||||||||||
| Blyton | 2 | 4.4 MW | – | ||||||||||||||||||||||||||
2 sites, 4.4 MW: 4.4 MW connected
| |||||||||||||||||||||||||||||
Not found in Northern Powergrid's September 2026 edition
17 sites last found at this grid supply point were not found in this edition by their MPAN, grid reference or name and postcode. QueueWatch keeps their pages for six months and does not say whether they have left the register.
- Chapel Lane BESS last found in the August 2026 edition
- Evolve Polymers last found in the August 2026 edition
- Evolve Polymers last found in the August 2026 edition
- Blyton Solar & BESS last found in the July 2026 edition
- Evolve Polymers last found in the July 2026 edition
- Evolve Polymers last found in the July 2026 edition
- Scawby Brook Energy last found in the July 2026 edition
- Vox Winterton BESS last found in the July 2026 edition
- Winterton PV last found in the July 2026 edition
- Evolve Polymers last found in the June 2026 edition
- Evolve Polymers last found in the June 2026 edition
- Evolve Polymers last found in the May 2026 edition
- Evolve Polymers last found in the May 2026 edition
- Evolve Polymers last found in the April 2026 edition
- Evolve Polymers last found in the April 2026 edition
- Evolve Polymers last found in the March 2026 edition
- Evolve Polymers last found in the March 2026 edition
What changed recently
Changes to the sites here found in both of two consecutive monthly editions, the latest first.
August 2026 edition to September 2026 edition: 63 sites matched. 6 sites at this grid supply point couldn't be matched between the two editions, because their details changed or they appear in only one.
- Warren Lane PhotovoltaicJune 2026 editionCapacity changed from 38 MW to 80 MW
- Warren Lane PhotovoltaicJune 2026 editionTechnology changed from Solar to Storage
Price what a delay would do to your project
QueueWatch reports what changed in the DNOs' published connection registers. It doesn't tell you what to do about it. That's what QueueQuant is for.
Give QueueQuant a site and it compares every way you could power it, on the grid or off it: waiting for the firm date, taking a non-firm offer, building a private wire or going off-grid, across every combination of contracted capacity, generation and battery. That’s millions of possible plans, each tested against thousands of possible futures for delay, curtailment and price. It returns the one plan that holds up best, even when that plan is not to build.
Get the plan that holds up best for your site, and where that answer flips.
What you get from QueueQuant
- The route to power that wins
- How to size every asset on the site
- The level of delay or curtailment at which that answer flips
- Whether the project is worth building at all
- How bad the worst outcomes get, at the risk level you choose
How power reaches a site
A grid supply point (GSP) is where the national grid hands power to the local network. A bulk supply point (BSP) steps it down to a lower voltage for an area. A primary substation steps it down again for the streets and sites nearby. Most small and medium sites connect at a primary. Not every network has all three levels.